HomeSolutionsServicesCommercialisationAboutInsightsTalk to SynapseAI
Industrial software

Control-room software, built by control engineers.

Three products. One is in service today; two are in development and described as such. Each addresses a problem we have watched cost plants money.

The products

What we build, and what state it is in.

Context

The problems these products are built against.

CONTROL KNOWLEDGE OPERATIONS ENGINEERING DATA MARKET SECURITY
CONTROL

Loops that underperform

Loops oscillate, sit in manual or drift — wearing valves, wasting energy and moving product quality around.

Select a node

01 · Available now

SynapseAI PID Tuner

A badly tuned loop rarely announces itself. It oscillates gently, sits in manual, or drifts — and because the plant still makes product, nobody fixes it. The Tuner turns a step test your team already has into tuning you can defend in a management-of-change review.

SynapseAI PID Tuner interface showing step-test analysis, identified FOPDT model, simulated closed-loop response and three tuning sets
Loop TIC-204 · reactor outlet temperature · data quality 92/100
How it works

Four stages, in the order an engineer would do them.

01

Assess the data

Nine checks run on the step test before any maths: sampling resolution, noise, baseline stability, settling window, step size and model fit. The result is a 0–100 confidence score. If the test cannot support dependable tuning, it says so and explains how to record a better one.

02

Identify the process

Automatic step detection, a two-point initial estimate, then non-linear least-squares refinement to a first-order-plus-dead-time model. Closed-loop identification is supported, so a test recorded with the controller in auto is usable — the loop does not have to go into manual.

03

Calculate and simulate

Six methods — IMC, Lambda, SIMC, Ziegler-Nichols, Cohen-Coon and AMIGO — with the appropriate one selected for the loop and the reasoning shown. Each candidate runs against the identified model through a discrete ISA PID with derivative-on-PV, derivative filtering, output clamping and anti-windup.

04

Hand over the numbers

Conservative, recommended and aggressive sets, each with overshoot, rise time, settling time, IAE and a maximum-sensitivity (Ms) figure. Values are formatted for the target controller, and a management-of-change report is produced in one step.

Engineering detail

The parts that decide whether tuning survives the shift.

Most retunes fail for unglamorous reasons: bad data taken at face value, the wrong controller form, a gain entered in the wrong units, or a valve problem treated as a tuning problem.

Data first

It does not assume the test is good

Give a typical tuner a poor step test and it returns confident, wrong numbers. This one scores the test before it calculates anything.

Robustness

Ms, not adjectives

Each set carries a maximum-sensitivity figure, so "conservative" and "aggressive" have a defensible engineering meaning rather than a marketing one.

Scaling

Engineering units to percent of span

It detects a PV in engineering units and normalises to percent of span, so the gain typed into the faceplate is the gain that was intended.

Loop types

Integrating and level loops

Flow, pressure and temperature, plus integrating level with a choice between tight control and averaging or surge damping.

Safety rules

Constraints built into the maths

Flow loops receive no derivative. Trip-adjacent loops suppress the aggressive set. Ziegler-Nichols and Cohen-Coon are detuned from their raw quarter-amplitude forms.

Mechanical faults

Stiction screening

It flags the mechanical signature of a sticking valve, because no set of gains has ever fixed one — and saying so is what earns an engineer's trust.

Integration

It speaks your controller's language.

Tuning constants are meaningless without the controller form and units they belong to. Values come out in the fields and units of the target system — which is where most retunes quietly go wrong, in the last metre between the calculation and the faceplate.

  • Siemens PCS 7 and S7
  • ABB 800xA
  • Honeywell Experion
  • Yokogawa CENTUM
  • Emerson DeltaV
  • Any controller in ISA (standard), series or parallel form
Deployment

Nothing to install. Nothing connected.

The engine runs in the browser from a single file. Step-test data stays on the machine — it is never uploaded, so there is nothing for IT or OT security to approve and no plant data leaving site. The software reads a recorded test; it never touches a running loop.

Offline
Runs client-side. No server, no account, no upload.
Read-only
No connection to the control system.
Next
A connected version reading a DCS, PLC or historian over OPC UA is in development.
Who it is for

Anyone responsible for how the loops behave.

01

Control & process engineers

Tuning more loops in less time, with the working shown.

02

Automation and E&I teams

Separating a tuning problem from a valve or instrument problem before the callout.

03

Operations and production

Fewer loops running in manual, and less variability on quality-critical measurements.

04

System integrators and EPCs

Defensible loop tuning at commissioning, with the documentation attached.

02 · In development

Digital O&M Logbook

Paper logs get lost, handwriting gets misread, and the context behind a decision disappears between crews. When an incident is investigated months later, the record that would explain it is a box of notebooks.

  • Shift handover with a structured, complete record
  • Permit tracking and operator notes against equipment
  • Search across shifts, units and date ranges
  • Reporting for operations and maintenance review
  • Audit trail suitable for use as compliance evidence
  • Usable on a tablet in the field, not only at a desk

Current availability: in development. We are working with sites that want to shape it.

Shift record · unit 200 Nights · 22:00–06:00
  1. 22:04 Handover in Crew of four. Two items carried over from days, both with an owner.
  2. 01:37 NoteP-311 Seal flush running low. Topped up and logged against the pump.
  3. 03:12 Issue raisedK-204 Vibration climbing on the outboard bearing. Trend attached to the entry.
  4. 03:40 ActionK-204 Assigned to day-shift mechanical, with the expectation written down.
  5. 05:55 Handover out Three open items, each owned. Signed by both supervisors.
5 entries2 assets tagged1 issue raised Audit trail complete
Illustrative · the Logbook is in development
One shift, in the order it is recorded
01
Shift start

Crew, state, open items.

02
Operator note

In the operator’s words.

03
Equipment status

Tagged to the asset.

04
Issue logged

Raised once, visible after.

05
Action assigned

Owner and expectation.

06
Handover

Structured, not prose at 06:00.

07
Audit trail

Evidence that stands up.

03 · In development

Plant Memory

A plant's real knowledge is not in one system. It is distributed across procedures, engineering documents, maintenance records, incident reports, shift notes and troubleshooting history — and the experience of people who may no longer be on site.

RAISED LOGGED BY SEEN BEFORE FIXED BY JUSTIFIES Compressor K-204 EQUIPMENT High vibration ALARM · 04:12 Operator note SHIFT LOG Previous incident INCIDENT REPORT Maintenance record CMMS WORK ORDER Decision & reasoning DECISION
EQUIPMENT

Compressor K-204

The asset the question is about. Everything below attaches to this tag, not to a folder somebody has to find.

Select a node
01

Where the knowledge sits

Procedures, P&IDs and engineering documents. Maintenance and reliability records. Incident and near-miss reports. Shift logs. Vendor manuals. The reasoning of the engineer who solved it last time.

02

What people actually need

Not a list of search results. The reasoning and the evidence behind a previous decision — what was tried, what was ruled out, and why.

03

What we are building

A system that brings those sources together and lets an engineer or operator ask a question in plain language, then shows the source documents behind the answer.

04

What we are not claiming

No downtime figures, no percentage improvements, no case studies. It is in development, it has not been proven at scale, and we will publish numbers when there is evidence for them.

Ask

Why was K‑204 taken off line in March, and what was ruled out first?

Answer, assembled from the record

Vibration on the outboard bearing climbed over three consecutive nights. Lube-oil supply was checked first and ruled out. The same vibration signature had already cost this machine a coupling, so the bearing was changed at the next window rather than run to the shutdown.

What the answer rests on
  • Shift logOperator notes, three nights running
  • P&ID · sheet 3Lube-oil circuit, as built
  • Incident reportEarlier coupling failure, same machine
  • Work orderBearing replaced, parts and crew recorded
Illustrative · Plant Memory is in development

Which loops are costing you, and how would you know?

Tell us what your control room struggles with. If the PID Tuner is not the right answer, we will say so.

Software FAQ

Questions about the software.

What is the SynapseAI PID Tuner?

PID tuning software that runs in a web browser. You give it a step test your team has already recorded. It scores the quality of that data, identifies a first-order-plus-dead-time model of the process, and returns three tuning sets — conservative, recommended and aggressive — each simulated against the identified model before you touch the plant.

Which control systems and DCS platforms does it support?

Tuning values are output ready to type into the faceplate for Siemens PCS 7 and S7, ABB 800xA, Honeywell Experion, Yokogawa CENTUM and Emerson DeltaV. It also supports any controller using the ISA (standard), series or parallel PID form, with the correct units and field names for each.

Does my process data leave my computer?

No. The engine runs locally in the browser from a single file. Step test data is never uploaded to a server, so there is nothing for IT or OT security to approve and no plant data leaving the site.

What data do I need to tune a loop?

A step test: a recorded change in controller output and the resulting process variable response, with timestamps. The Tuner runs nine data quality checks on that file first — sampling resolution, noise, baseline stability, settling window, step size and model fit — and gives a 0 to 100 confidence score before it produces any tuning.

Can it handle level and other integrating loops?

Yes. Alongside flow, pressure and temperature, it handles integrating level control with a choice between tight control and averaging or surge damping. It also supports closed-loop identification, so you can work from a test taken with the controller in auto rather than dropping the loop into manual.

Does the PID Tuner connect to my DCS or historian?

Not in the current version. Today it works from an exported file. A connected version that reads directly from a DCS, PLC or historian over OPC UA is in development, which will add on-demand loop analysis and fleet-wide loop health monitoring.

Is Plant Memory available yet?

No. Plant Memory is in development. A small number of sites are working with us to shape it. We do not publish performance figures for it because there is not yet evidence to support them.